Building wires and cables are evaluated according to EN13501-6 Standard Test and fire rating. The European Union market requires a minimum rating of class Eca or above for the fireproof grade of building wire and cable as the minimum requirement. According to the heat release rate of wire and cable and the length of combustion destruction, the EN13501-6 standard divides the flame protection of cables into seven grades, namely, EN13501-6, Aca, B1ca, B2ca, Cca, Dca, Eca and Fca, these seven grades. Nanjing SMART company to share wire and cable EN13501-6 fire rating, Eca level testing standards and data requirements. Tel: +86 25-8658 3475.
EN13501-6 Class Eca
A cable product applying for class Eca shall be tested in accordance with EN 60332-1-2. EN13501-6 Class Eca requirement: The results of H≤425mm
EN 13501-6:2014 Fire classification of construction products and building elements. Classification using data from reaction to fire tests on electric cables. BS EN 13501-6:2014 Status: Current;Published: March 2014。
EN13501-6 main test standard
EN ISO 1716: Heat of combustion test
EN 60332-1-2: Vertical flame spread of single cable
EN 50399: Buring behaviour and smoke production of bunched cable
EN 61034-2: Smoke production of burning cable
EN 50267-2-3: Acidity of gases producted by burning cables